Determination of Capacitor Size

 

Example : What value of capacitor KVAR is required to improve the P.F. of a 1000 KW load from 0.7 to 0.95 power Factor? >> From the table the multiplying factor for improving the p.f. from 0.7 to 0.95 is 0.691. Capacitor rating required = 1000 *0.691 = 691 KVAR.